Common mistakes — Eco Sistems gateway ​

General CanCan problems (LED codes, box invisible on the bus, firmware update) are in Common mistakes. This chapter is what goes wrong with the watermaker side.

Nothing at all on device/20/… ​

The gateway publishes only while it is hearing the watermaker. A silent topic means the second bus is not carrying anything the gateway can hear.

Likely causeHow to tellFix
The watermaker bus is not at 250 kbit/stotal silence rather than errorsthe gateway forces 250 kbit/s at every start and it cannot be changed — set the watermaker side to match
CAN 2 wiring or termination60 Ω across a powered-down busone 120 Ω at each physical end of the watermaker bus, nowhere else
CAN 1 and CAN 2 swappedthe box itself is invisible on the MUXEN bus tooCAN 1 is always the MUXEN bus
The watermaker is off or its controller is not powerednothing on the bus at allpower it up
You are watching the wrong instancethe box was renumbered, or never wasthe factory instance of the watermaker device is 0, not 255

The values freeze, then the device vanishes from the screens ​

The gateway declares the unit absent after 5 seconds without a frame and stops publishing; the Brain keeps the last payload for about 30 seconds before marking it stale. A watermaker that flickers in and out of the screens is one whose frames are not arriving reliably — suspect the second bus, its termination or a loose connector, not the gateway.

A command from the boat does nothing ​

Likely causeHow to tellFix
The unit is not being heardnothing published on device/20/<n>/lifeevery command is dropped while the unit is absent — fix reception first
Two commands sent too close togetherthe second one appears to vanishthe gateway refuses anything sent less than 200 ms after the previous command; leave a second between them
Flow up/down while not producingthe unit is in standby or rinsingthose two commands are accepted only during production
Flow down already at the minimumFlowNowRateFromMaxFlow is at its lowestthe gateway refuses to lower the flow below the unit's minimum
The command payload was not understoodthe watermaker stops insteada payload with none of the recognised keys is read as stop — check the spelling of produce, rinsing, off, productionFlowUp, productionFlowDown
The unit itself refusedthe command left, but state never changesthe watermaker decides: pressure, tank level, its own safety logic. Look at the unit's panel

Remember that state is reported by the watermaker. The gateway never anticipates a command it has sent.

Two watermakers answer the same command ​

The watermaker device of this gateway is instance 0 out of the factory. Fit two Eco Sistems gateways without renumbering them and both answer every command sent to device/20/0, and their values alternate on the screens.

sh
muxen-uds -i can0 scan

Each function + instance pair must appear once. Renumber one of them and reboot it — see Commissioning.

The instance number I wrote seems to be ignored ​

The box reads its instance numbers once, at startup. Write with --reboot, or power-cycle the box after writing.

The litre counter went back to zero ​

It is the watermaker's own counter, forwarded as is, and it is a 16-bit value: it wraps to 0 after 65 535 l. It also reads 0 whenever the gateway is not hearing the unit. The gateway stores nothing and totals nothing — long-term totals belong on the Brain.

The flow percentage never leaves 50 – 100 % ​

That is deliberate. The published FlowNowRateFromMaxFlow is trimmed to the range the unit really works in: below 50 % it reads 50, above 95 % it reads 100, and it reads 100 whenever the unit is not producing. Do not build a screen expecting 0 – 100 %.

Pressures, pumps and the hour meter all read zero ​

The MUXEN watermaker device can carry pre-filter and high pressure, pump and valve states, fuses and an hour meter. This equipment does not provide them, so the state topic is published with every field at zero. Read the life topic — state, salinity, flow, litres — and ignore device/20/<n>/state.

An alarm appeared and I cannot tell which ​

The unit reports one alarm at a time, and the gateway republishes it on device/20/<n>/error/<code>: 23 pressure too high, 24 no flow, 25 salinity too high. As soon as the unit reports no alarm, the gateway clears the faults it is holding.

The relays and the inputs of the box do nothing ​

Give the generic I/O device (function 17) an instance number — at 255 it publishes nothing and cannot be addressed. On this firmware it starts publishing as soon as it has a number; EnGenIo is accepted but has no effect here, so there is nothing else to enable.

That routine is not implemented on this firmware; the request is refused. Identify the box by its UID (muxen-uds -i can0 uid --scan), not by locate.

WatermakerModel will not stay on the value I wrote ​

It cannot be changed: the firmware sets it back to the Eco Sistems 48 V model every time it starts. That is what tells the boat's screens which watermaker they are talking to.