General CanCan problems (LED codes, box invisible on the bus, firmware update) are in Common mistakes. This chapter is what goes wrong with the watermaker side.
Nothing at all on device/20/…
The gateway publishes only while it is hearing the watermaker. A silent topic means the second bus is not carrying anything the gateway can hear.
| Likely cause | How to tell | Fix |
|---|---|---|
| The watermaker bus is not at 250 kbit/s | total silence rather than errors | the gateway forces 250 kbit/s at every start and it cannot be changed — set the watermaker side to match |
| CAN 2 wiring or termination | 60 Ω across a powered-down bus | one 120 Ω at each physical end of the watermaker bus, nowhere else |
| CAN 1 and CAN 2 swapped | the box itself is invisible on the MUXEN bus too | CAN 1 is always the MUXEN bus |
| The watermaker is off or its controller is not powered | nothing on the bus at all | power it up |
| You are watching the wrong instance | the box was renumbered, or never was | the factory instance of the watermaker device is 0, not 255 |
The values freeze, then the device vanishes from the screens
The gateway declares the unit absent after 5 seconds without a frame and stops publishing; the Brain keeps the last payload for about 30 seconds before marking it stale. A watermaker that flickers in and out of the screens is one whose frames are not arriving reliably — suspect the second bus, its termination or a loose connector, not the gateway.
A command from the boat does nothing
| Likely cause | How to tell | Fix |
|---|---|---|
| The unit is not being heard | nothing published on device/20/<n>/life | every command is dropped while the unit is absent — fix reception first |
| Two commands sent too close together | the second one appears to vanish | the gateway refuses anything sent less than 200 ms after the previous command; leave a second between them |
| Flow up/down while not producing | the unit is in standby or rinsing | those two commands are accepted only during production |
| Flow down already at the minimum | FlowNowRateFromMaxFlow is at its lowest | the gateway refuses to lower the flow below the unit's minimum |
| The command payload was not understood | the watermaker stops instead | a payload with none of the recognised keys is read as stop — check the spelling of produce, rinsing, off, productionFlowUp, productionFlowDown |
| The unit itself refused | the command left, but state never changes | the watermaker decides: pressure, tank level, its own safety logic. Look at the unit's panel |
Remember that state is reported by the watermaker. The gateway never anticipates a command it has sent.
Two watermakers answer the same command
The watermaker device of this gateway is instance 0 out of the factory. Fit two Eco Sistems gateways without renumbering them and both answer every command sent to device/20/0, and their values alternate on the screens.
sh
muxen-uds -i can0 scanEach function + instance pair must appear once. Renumber one of them and reboot it — see Commissioning.
The instance number I wrote seems to be ignored
The box reads its instance numbers once, at startup. Write with --reboot, or power-cycle the box after writing.
The litre counter went back to zero
It is the watermaker's own counter, forwarded as is, and it is a 16-bit value: it wraps to 0 after 65 535 l. It also reads 0 whenever the gateway is not hearing the unit. The gateway stores nothing and totals nothing — long-term totals belong on the Brain.
The flow percentage never leaves 50 – 100 %
That is deliberate. The published FlowNowRateFromMaxFlow is trimmed to the range the unit really works in: below 50 % it reads 50, above 95 % it reads 100, and it reads 100 whenever the unit is not producing. Do not build a screen expecting 0 – 100 %.
Pressures, pumps and the hour meter all read zero
The MUXEN watermaker device can carry pre-filter and high pressure, pump and valve states, fuses and an hour meter. This equipment does not provide them, so the state topic is published with every field at zero. Read the life topic — state, salinity, flow, litres — and ignore device/20/<n>/state.
An alarm appeared and I cannot tell which
The unit reports one alarm at a time, and the gateway republishes it on device/20/<n>/error/<code>: 23 pressure too high, 24 no flow, 25 salinity too high. As soon as the unit reports no alarm, the gateway clears the faults it is holding.
The relays and the inputs of the box do nothing
Give the generic I/O device (function 17) an instance number — at 255 it publishes nothing and cannot be addressed. On this firmware it starts publishing as soon as it has a number; EnGenIo is accepted but has no effect here, so there is nothing else to enable.
muxen-uds locate does not blink the box
That routine is not implemented on this firmware; the request is refused. Identify the box by its UID (muxen-uds -i can0 uid --scan), not by locate.
WatermakerModel will not stay on the value I wrote
It cannot be changed: the firmware sets it back to the Eco Sistems 48 V model every time it starts. That is what tells the boat's screens which watermaker they are talking to.