What you need ​

The gateway ​

One MUXEN serial gateway running the VE.Direct firmware, product ID 010010002 — either generation. Both have the same four ports and behave the same way; see VE.Direct gateway (010010002) — Overview for the two images.

On the Victron side ​

Working Victron equipmentalready installed, powered and configured with the Victron tools. The gateway reads a device; it does not set it up
Equipment the gateway knowsMPPT solar chargers, battery monitors and shunts, Phoenix inverters, chargers, buck-boost DC/DC converters. The identifiers are listed in Reference — VE.Direct gateway
One VE.Direct cable per deviceVE.Direct is point to point. Two devices cannot share a port, and one device cannot feed two ports

If you are unsure whether a device is supported, read its VE.Direct output before ordering anything: the first line of every block is PID, and that value is the only thing the gateway matches on.

Wiring ​

ConnectorGoes toSpeed
CANthe boat's MUXEN bus500 kbit/s
Ports 1 to 4one Victron VE.Direct port each19 200 baud, 8 data bits, no parity, 1 stop bit — fixed by the firmware

The serial parameters are the VE.Direct standard and there is no parameter for them. Both directions are used: the Victron device sends its text block continuously, and the gateway sends the on/off command back down the same cable.

The MUXEN bus is an ordinary 120 Ω CAN bus: two wires and a common ground, one 120 Ω termination at each physical end of the bus and nowhere else. The gateway is terminated only if it happens to be at the end of a segment.

The four VE.Direct ports are electrically separate from the MUXEN bus, and separate from each other. A fault on one port takes out one device, not the box.

Which port is which ​

The ports are numbered 1 to 4 in connector order, and the numbering matters: the first time a device is seen on a port, the MUXEN instance it gets is the port number minus one.

PortInstance given on first sight
10
21
32
43

So four MPPTs plugged into ports 1 to 4 come up as solar chargers 0, 1, 2 and 3 with nothing to configure. You can renumber them afterwards — read Common mistakes — VE.Direct gateway first, because renumbering has one trap.

The box's own inputs and outputs ​

One relay and one analog input, independent of the VE.Direct function. The relay can be driven from the MUXEN bus by a command frame, or by an equation written into Relay1Eqn and evaluated from what passes on the bus. The box's own I/O frame is not published by default (EnGenIo = 0); the relay works either way. See Reference — VE.Direct gateway.