What you need ​

The gateway ​

One serial gateway running the Blue Airco firmware, product ID 010010028. Two hardwares carry it:

Hardware
990010063CAN/Serial v2the production board — use this one for a new installation
990010053CAN/Modbusno longer built, still supported on boats that have one

Both have four serial ports and one MUXEN CAN connector. The firmware behaves identically on the two.

On the Blue Airco side ​

Blue Airco units with their own controllerthe machines keep their own panel and their own protections. The gateway reads what the controller answers and writes back the same on/off and set-point the panel writes
A Modbus RTU connection per unittwo wires and a common ground, brought to one of the gateway's four serial ports

The air conditioning must be installed, commissioned and working before the gateway is fitted. The gateway polls a Modbus line; it does not set up an air conditioner.

Both generations are recognised — the EVO units and the pre-EVO ones — and the gateway works out which is which by itself. Nothing has to be declared.

Wiring ​

ConnectorGoes toSpeed
CANthe boat's MUXEN bus500 kbit/s
Serial 1 … 4one Blue Airco unit each9600 8N1 — fixed by the firmware

Each serial port is driven as a 2-wire half-duplex RS-485 line, and the firmware switches the on-board line termination on at every start. Neither can be changed by configuration, so the unit at the far end must be at 9600 bauds, 8 data bits, no parity, 1 stop bit, and it must be the only device on that line.

One unit per port

Every port talks to Modbus slave address 1 and only to that address. Two units on one line both answer, and the port sees garbage. Set every unit to address 1 and give each its own port.

Ports are independent: a unit lost on one port changes nothing on the other three, and each port keeps its own MUXEN identity.

The MUXEN bus is an ordinary 120 Ω CAN bus: two wires and a common ground, one 120 Ω termination at each physical end and nowhere else. The gateway is terminated on that side only if it happens to be at the end of a segment.

The MUXEN bus and the Modbus lines stay electrically separate. Nothing from the MUXEN bus reaches a unit except the on/off and set-point writes this firmware deliberately translates.

The box's own inputs and outputs ​

This firmware exposes, as a separate generic I/O device:

One relaydriven from the MUXEN bus, channel 0
One analog inputreported in millivolts

They are independent of the air-conditioning function. Give the I/O device an instance number of its own, and set EnGenIo to 1 — it publishes nothing until you do. See Reference.

Power and the batteries ​

The gateway switches a unit off on its own when the battery park that unit is bound to is in trouble — see Commissioning, step 6. Decide at wiring time which park each unit belongs to, or leave it standalone and the gateway will never stop it for an electrical reason.

Integration of multiplexed solutions