This chapter covers what goes wrong on any CanCan, whatever its application. Problems specific to one kind of equipment are in that application's own FAQ.
Read the LED first
The box has one LED and it is worth ten minutes of bus tracing.
| The LED | The box is | What to do |
|---|---|---|
| blinking once a second | running normally | the fault is elsewhere — bus, settings, or the equipment |
| flashing very fast (≈25 Hz) | refusing to confirm its own firmware | power-cycle it: the previous firmware comes back. Then check the image — see Loading and updating a firmware |
| steady on, never blinking | stuck during startup, before it began running | power-cycle it once. If it comes back the same way, note the product ID and software version and report it — it does not fix itself |
| off, with the box powered | not starting | hardware fault or no firmware — factory programming needed |
| blinking at some other rate | in an application-specific error | see that application's manual |
The box does not appear on the bus at all
| Likely cause | How to tell | Fix |
|---|---|---|
| It has never been given an instance number | a factory box ships with InstanceNum = 255, which means "not addressed" — it answers a UID scan but publishes nothing | muxen-uds -i can0 uid --scan, then write an instance number |
| The MUXEN bus is not terminated correctly | 60 Ω across a powered-down bus; anything near 120 Ω or 40 Ω is wrong | one 120 Ω at each physical end, nowhere else |
| No power, or CAN 1 not wired | LED off | check supply and the CAN 1 connector |
| Wrong side | CAN 1 is the MUXEN bus, CAN 2 the equipment | swap the connectors |
A box with no instance number is not broken and does not need reprogramming. It is waiting to be told who it is.
Two boxes fight over the same identity
Two devices with the same function and the same instance number on one bus produce values that jump between two sources, alarms that clear themselves, commands that reach the wrong box. It happens whenever a second gateway is added with the settings of the first, or a spare box is installed without being reconfigured.
muxen-uds -i can0 scan lists what is on the bus. Each function + instance pair must appear once.
Two unconfigured boxes can collide on their own: the watermaker, propulsion-motor and Magic Trim device types default to instance 0 rather than 255, so they publish from the first power-up. Fit and number them one at a time.
Nothing arrives from the equipment (CAN 2)
| Likely cause | Fix |
|---|---|
| Bitrate mismatch | each application fixes the speed its equipment uses; if the equipment is configurable, it must match — see the application manual |
| Equipment bus not terminated | 120 Ω at each end of that segment too |
| The equipment is off, asleep, or in a mode where it says nothing | power it up and make it do something |
| Wrong firmware for that equipment | check ProductId against the catalogue in CanCan gateways — Overview |
The relays or the inputs do nothing
| Symptom | Cause | Fix |
|---|---|---|
| the box's own I/O never appears on the bus | EnGenIo is 0 by default — the generic I/O device is off until enabled | set EnGenIo to 1 and give the I/O device an instance number |
| the analog inputs read 0 mV | the sensor supply is off (EnAnalogPwr = 0) or the sensor is not wired | set EnAnalogPwr to 1, check the sensor |
| a dry-contact input never activates | it is closed to ground, not to +12 V | rewire; no external pull-up is needed |
A setting I changed has no effect
Every parameter on every CanCan takes effect only after a restart. Writing a setting stores it; the box reads its settings once, when it starts, and works from that copy until it is restarted. Nothing rejects the write, nothing warns you, and reading the parameter back shows the new value — the box is simply still running on the old one.
Always write with --reboot:
sh
muxen-uds -i can0 -d <address> writeconfig --name <name> --value <value> --rebootIf you changed several settings without it, one restart at the end applies them all.
After a factory reset, the box has disappeared again
The factory-reset routine restores every parameter to its default. All the pairing, all the calibration, all the application settings are gone. The instance number can be kept or reset depending on how the routine is called — and if it was reset, the box goes back to 255 and stops publishing.
There is no undo. Read the configuration out and keep it before resetting anything:
sh
muxen-uds -i can0 -d <address> readconfigThe firmware update failed
Nothing is damaged. The box is still running the firmware it had before — that is by design, see Loading and updating a firmware. The usual causes, in order: an image for the other hardware generation (5.x versus 6.x), a bus interrupted during the transfer, or the wrong product ID. Check the version and hardware ID of the box, pick the matching image, retry.